VRF Modular Series

DC Inverter Modular Series

ModelRCOF252FR1RCOF280FR1RCOF335FR1RCOF400FR1RCOF450FR1RCOF500FR1
CapacityCoolingkW25,528,033,540,045,050,0
Heating27,431,537,545,050,056,0
EER/COPW4,35 / 4,664,04 / 4,383,95 / 4,263,78 / 4,103,54 / 4,023,46 / 3,96
Power supplyF, V, Hz3F, 380~415V, 50Hz
Power inputCoolingkW5,796,938,4810,5812,7114,45
Heating5,887,198,8010,9812,4414,14
Refrigerant charge volumekg10,0010,0012,0015,0015,0016,00
CompressorTypeScroll
Quantityunit111222
Outline dimensionH x W x Dmm1618 x 974 x 7661618 x 974 x 7661618 x 1264 x 7661618 x 1264 x 7661618 x 1264 x 7661618 x 1264 x 766
Package dimensionH x W x Dmm1750 x 1030 x 8251618 x 1264 x 7661750 x 1315 x 8251750 x 1315 x 8251750 x 1315 x 8251750 x 1315 x 825
WeightNet / Grosskg190190225270270310
Sound pressure leveldB585858606060
Operating temperatureCooling°C-5~+50°C-5~+50°C-5~+50°C-5~+50°C-5~+50°C-5~+50°C
Heating-20~+28°C-20~+28°C-20~+28°C-20~+28°C-20~+28°C-20~+28°C
Piping connectionGasmm (in)22,225,428,628,628,631,8
Liquidmm (in)12,712,712,715,915,915,9
Maximum indoor unitQuantityunit131620232629
Maximum total length of fitting pipem200200200200200200
Cooling: indoor temperature t=27​°C DB, t=19​°C WB, outdoor temperature t=35​°C DB, t=24​°C WB.
Heating: indoor temperature t=20​°C DB, t=15​°C WB, outdoor temperature t=7​°C DB, t=6​°C WB.
The above data may be changed without notice for future improvement on quality and performance.

VRF
Systems

  • Release date: 2017-08-07