Fan Coil Units

Description

Fan coil unit is a kind of compound device which assemble fan and surface-type coil heating-exchanger together. Fan coil has horizontal type, vertical type, etc. A cooling (heating) supply system usually consists of fan coil terminals and chilled water system (heated water system).

REFRA commercial fan coil is designed and manufactured on the base of advanced technology, and utilize qualified galvanized iron as material. Due to its supper-thin design, it has such advantages: beautiful outlook, space saving, easy installation, etc. And the most obvious advantage is that it can decrease the outlet air Temp-difference as low as possible to make room more comfortable, as well as don’t decrease cooling capacity output. For the large air flow volume design, it can increase room ventilation frequency, supply more flesh air, and balance room temperature distribution. Benefiting from adoption of advanced material and technology, it can effectively decrease the running noise and keep running smoothly. With the advantages above, it can be widely applied in market, hospital, office building, hotel airport, etc.

Wall Mounted Type Fan Coil Unit 2-pipe

ModelRGWS021ARRGWS027ARRGWS036ARRGWS042AR
CapacityCoolingkW2,102,703,604,20
HeatingkW3,154,055,406,30
Air flowm3/h360 / 322 / 282550 / 413 / 367680 / 591 / 532850 / 708 / 616
Power supplyTypeV, Ph, Hz220-240V ~ 1Ph - 50Hz
InputW50506060
Water systemWater flow volumem3/h0,400,450,600,70
Pressure dropkPa13244445
CoilOperating pressureMPa≤ 1,5 MPa≤ 1,5 MPa≤ 1,5 MPa≤ 1,5 MPa
MotorPower outputW20202020
Sound pressure levelH / M / LdB(A)38 / 35 / 2940 / 36 / 3043 / 38 / 3248 / 41 / 36
Piping ConnectionWater inlet | outletin1/2 | 1/21/2 | 1/21/2 | 1/21/2 | 1/2
Condensing water drainmm15,615,615,615,6
DimensionOutline (H x W x D)mm275 x 845 x 180275 x 845 x 180298 x 940 x 200298 x 940 x 200
Package (H x W x D)mm355 x 915 x 255355 x 915 x 255380 x 1010 x 285380 x 1010 x 285
WeightNetkg11111313
Grosskg14141717
Standard optionWireless remote controll

Optional: RGS2T2V (2-way valve); RGS2T3V (3-way valve)

Cooling: 12/7°C inlet/outlet water temperature; 27°C db/19°C wb inlet air temperature.
Heating: 60°C inlet water temperature; 20°C inlet air temperature.
The above data may be changed without notice for future improvement on quality and performance.

Cassette Type Fan Coil Unit 2-pipe

ModelUnitRCWK300ARRCWK380ARRCWK470ARRCWK600ARRCWK720ARRCWK850ARRCWK900AR
PanelRCKPWCRCKPWCRCKPWCRCKPWBRCKPWBRCKPWBRCKPWB
CapacityCoolingkW2,803,504,505,307,208,5010,00
HeatingkW4,205,306,808,0010,8012,8015,00
Air flowH / M / Lm3/h500 / 434 / 306600 / 506 / 357800/ 679 / 4791000 / 867 / 6121300 / 1098 / 7751500 / 1272 / 8981700 / 1445 / 1020
Power supplyV, Ph, Hz220-240V ~ 1Ph - 50Hz
Water systemWater flow volumem3/h0,480,600,781,101,241,461,55
Pressure dropkPa25283036303840
Sound pressure levelH / M / LdB(A)40 / 37 / 3544 / 41 / 3844 / 41 / 3844 / 41 / 3847 / 44 / 4156 / 52 / 4856 / 52 / 48
Piping ConnectionWater inlet / outletmm20 / 2020 / 2020 / 2020 / 2020 / 2020 / 2020 / 20
Condensing water drainmm25252525252525
DimensionOutline (H x W x D)mm275 x 580 x 580275 x 580 x 580275 x 580 x 580230 x 840 x 840230 x 840 x 840285 x 840 x 840285 x 840 x 840
Package (H x W x D)mm350 x 745 x 675350 x 745 x 675350 x 745 x 675310 x 920 x 920310 x 920 x 920375 x 920 x 920375 x 920 x 920
Weight Nett/Grosskg22,0 / 24,022,0 / 24,022,0 / 24,028,0 / 32,028,0 / 32,040,0 / 44,040,0 / 44,0
Panel dimensionOutline (H x W x D)mm30 x 650 x 65030 x 650 x 65030 x 650 x 65050 x 950 x 95050 x 950 x 95050 x 950 x 95050 x 950 x 950
Package (H x W x D)mm120 x 710 x 710120 x 710 x 710120 x 710 x 710105 x 1030 x 1030105 x 1030 x 1030105 x 1030 x 1030105 x 1030 x 1030
Weight Nett/Grosskg4,0 / 5,04,0 / 5,04,0 / 5,05,0 / 7,05,0 / 7,05,0 / 7,05,0 / 7,0
Standard optionWireless remote control

Optional: RCK2T3V (3-way valve)

Cooling: 12/7°C inlet/outlet water temperature; 27°C db/19°C wb inlet air temperature.
Heating: 60°C inlet water temperature; 20°C inlet air temperature.
The above data may be changed without notice for future improvement on quality and performance.

Concealed Ceiling Type 2-pipes Fan Coil Unit

ModelRCWD022ARRCWD033ARRCWD042ARRCWD045ARRCWD058ARRCWD079ARRCWD091ARRCWD108ARRCWD126AR
CapacityCoolingkW2,133,264,174,845,817,929,0711,4913,00
HeatingkW3,485,326,817,919,9813,5916,0220,2922,56
Air flowH / M / Lm3/h340 / 285 / 210510 / 420 / 320680 / 580 / 420850 / 700 / 5201020 / 840 / 6201360 / 1150 / 8401700 / 1400 / 10002040 / 1650 / 12502380 / 2000 / 1480
Power supplyV, Ph, Hz220-240V ~ 1Ph - 50Hz
ESPPa121212123030303030
Water systemWater flow volumem3/h0,370,560,720,831,001,361,561,972,24
Pressure dropkPa142022243434404250
Sound pressuredB(A)384042464747505152
Piping ConnectionWater inlet / outletin3/4 / 3/43/4 / 3/43/4 / 3/43/4 / 3/43/4 / 3/43/4 / 3/43/4 / 3/43/4 / 3/43/4 / 3/4
Condensing water drainin3/43/43/43/43/43/43/43/43/4
DimensionH x W x Dmm240 x 770 x 472240 x 827 x 472240 x 927 x 472240 x 927 x 472240 x 1140 x 472240 x 1440 x 472240 x 1546 x 472240 x 1835 x 472240 x 1835 x 472
Weightkg13,015,017,017,020,027,032,036,036,0

Optional: AE-Y308 (wired controller with LCD); RCK2TV3 (3-way valve).

Cooling: 12/7°C inlet/outlet water temperature; 27°C db/19°C wb inlet air temperature.
Heating: 60°C inlet water temperature; 20°C inlet air temperature.
The above data may be changed without notice for future improvement on quality and performance.